Remove The Faulted Internal M.2 Boot Module - Dell PowerStore 1000 Installation And Service Manual

Table of Contents

Advertisement

Figure 119. Removing the top cover

Remove the faulted internal M.2 boot module

Steps
1. Locate the M.2 boot module adaptor in the node.
You can identify the M.2 boot module adaptor by the blue retaining tabs.
2. Press the blue retaining tabs downward to free the M.2 boot module adaptor from its slot.
3. Touching only the outside edges of the M.2 boot module adaptor, remove the M.2 boot module adaptor.
Figure 120. Removing the M.2 boot module adaptor
4. Identify the faulted internal M.2 boot module. One internal M.2 boot module is labeled DRIVE 0 and the other is
labeled DRIVE 1. In PowerStore Manager, DRIVE 0 is identified as InternalM.2BootModule0 and DRIVE 1 is identified as
InternalM.2BootModule1.
5. On the faulted internal M.2 boot module, gently pull the handle on the release tab to separate it from the tab holding it in
place.
6. Gently pull straight up on the pull tab to free it from the M.2 boot module adaptor.
7. Remove the internal M.2 boot module from the M.2 boot module adaptor.
104
Base enclosure service procedures