Hitachi Relion 670 Series Applications Manual page 243

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK506375-UEN Rev. N
double busbar arrangement without transfer busbar or a single busbar arrangement with/without
transfer busbar.
QB1
QA1
QB9
IEC04000478 V1 EN-US
Figure 92:
The signals from other bays connected to the module ABC_LINE are described below.
12.4.2.2
Signals from bypass busbar
To derive the signals:
Signal
BB7_D_OP
VP_BB7_D
EXDU_BPB
These signals from each line bay (ABC_LINE) except that of the own bay are needed:
Signal
QB7OPTR
VPQB7TR
EXDU_BPB
For bay n, these conditions are valid:
Railway application RER670
Application manual
WA1 (A)
WA2 (B)
WA7 (C)
QB2
QB7
QC1
QC2
QC9
en04000478.vsd
Switchyard layout ABC_LINE
All line disconnectors on bypass WA7 except in the own bay are open.
The switch status of disconnectors on bypass busbar WA7 are valid.
No transmission error from any bay containing disconnectors on bypass busbar WA7
Q7 is open
The switch status for QB7 is valid.
No transmission error from the bay that contains the above information.
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12
Control
M13560-4 v5
M13560-6 v5
237