12.11.3
Setting guidelines
The parameters for Single command, 16 inputs (SINGLECMD) are set via the local HMI or PCM600.
Parameters to be set are MODE, common for the whole block, and CMDOUTy which includes the
user defined name for each output signal. The MODE input sets the outputs to be one of the types
Off, Steady, or Pulse.
Off, sets all outputs to 0, independent of the values sent from the station level, that is, the
operator station or remote-control gateway.
Steady, sets the outputs to a steady signal 0 or 1, depending on the values sent from the station
level.
Pulse, gives a pulse with 100 ms duration, if a value sent from the station level is changed from
0 to 1. That means the configured logic connected to the command function block may not have
a cycle time longer than the cycle time for the command function block.
12.12
Transformer energizing control XENCPOW
12.12.1
Identification
Function description
Transformer Energizing Control
12.12.2
Application
The transformer core may become saturated due to an abrupt change in the voltage applied to it.
This may be caused by:
Railway application RER670
Application manual
Single
command
function
SINGLESMD
CMDOUTy
OUTy
Application example showing a logic diagram for control of external devices via
configuration logic circuits
IEC 61850
identification
XENCPOW
© 2017 - 2023 Hitachi Energy. All rights reserved
Configuration logic circuits
&
User-
defined
conditions
IEC 60617
identification
0->1T
IEC15000180 V1 EN-US
Section 12
en04000208.vsd
GUID-0AC48962-6A23-4ED7-8263-7B449BED54E2 v1
GUID-E3009E9F-7AE2-472F-A7E6-F2245626CFA3 v1
ANSI/IEEE C37.2
device number
25T
GUID-11110C3C-33A3-4B36-9D85-F112334B29D1 v2
Control
M12448-3 v3
275

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer670

Table of Contents