The base currents for T1PPDIF functions are set under Global Base Values in Parameter Setting
tool.
6.2.5.1
Application examples
Five examples of railway power transformer connections are presented here. Other transformer
connections may also be protected using the single-phase T1PPDIF function.
Transformer connection – example 1
132/15kV
U
V
IEC15000170 V3 EN-US
Figure 34:
Base current calculation:
I
Base
_
Wx
IECEQUATION058 V1 EN-US
Railway application RER670
Application manual
1000
SBase
121
A
UBase
W
1
1000
SBase
1067
A
UBase
W
2
Rated power of transformer [MVA]
Rated phase-to-phase voltage of winding 1 [kV]
Rated phase-to-phase voltage of winding 2 [kV]
In all the following figures the phases are indicated as U and V on the HV side and R and
S on the LV side of the transformer. Equivalent winding ends are U & R and V & S.
I
U
132kV
I
v
Transformer connection – example 1
1000
S
MVA
 
U
kV
Ph
_
Ph
_
Wx
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6
Differential protection
(Equation 4)
(Equation 5)
GUID-BAC97BE4-C678-435E-ACEE-7C90BB276E58 v2
GUID-0C1EBB70-8FBB-4AB9-8101-6E16B265FD7D v2
R
15kV
I
s
S
IEC15000170-3-en.vsdx
(Equation 6)
79