1MRK506375-UEN Rev. N
BB7_D_OP = 1
BC_17_OP = 1
BC_17_CL = 0
BC_27_OP = 1
BC_27_CL = 0
EXDU_BPB = 1
VP_BB7_D = 1
VP_BC_17 = 1
VP_BC_27 = 1
If there is no second busbar WA2 and therefore no QB2 disconnector, then the interlocking for QB2
is not used. The state for QB2, QC21, BC_12, BC_27 are set to open by setting the appropriate
module inputs as follows. In the functional block diagram, 0 and 1 are designated 0=FALSE and
1=TRUE:
QB2_OP = 1
QB2_CL = 0
QC21_OP = 1
QC21_CL = 0
BC_12_CL = 0
BC_27_OP = 1
BC_27_CL = 0
VP_BC_12 = 1
12.4.3
Interlocking for bus-coupler bay ABC_BC
12.4.3.1
Application
The interlocking for bus-coupler bay (ABC_BC) function is used for a bus-coupler bay connected to a
double busbar arrangement according to figure 96. The function can also be used for a single busbar
arrangement with transfer busbar or double busbar arrangement without transfer busbar.
QB1
QA1
IEC04000514 V1 EN-US
Figure 96:
Railway application RER670
Application manual
QB2
QB20
QB7
QC1
QC2
en04000514.vsd
Switchyard layout ABC_BC
© 2017 - 2023 Hitachi Energy. All rights reserved
WA1 (A)
WA2 (B)
WA7 (C)
Section 12
Control
IP14144-1 v2
M13555-3 v8
241