Hitachi Relion 670 Series Applications Manual page 298

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 14
Logic
This signal can also be used for other purposes internally in the IED. An example could be the
starting of breaker failure protection.
Set the required length of the trip pulse to for example, tTripMin = 150 ms.
For special applications such as lockout refer to the separate section below. The typical connection is
shown below in
Impedance protection zone 1 TRIP
Impedance protection zone 3 TRIP
Impedance protection zone 2 TRIP
IEC16000184 V3 EN-US
Figure 145:
14.1.3.2
Lock-out
The SMPPTRC function block is provided with possibilities to initiate lockout. The lockout can be set
to only activate the circuit breaker lockout output CLLKOUT or to both initiate the circuit breaker
lockout output and to maintain the trip signal output TRIP (latched).
If external conditions are required to initiate a circuit breaker lockout, it can be achieved by activating
input SETLKOUT. The setting AutoLock = Off means that the internal trip will not activate lockout so
only initiation of the input SETLKOUT will result in lockout. This is normally the case for overhead line
protection where most faults are transient. Unsuccessful autoreclosing and back-up zone tripping can
in such cases be connected to initiate lockout by activating the input SETLKOUT.
If CLLKOUT is set by an external trip signal from another protection function, that is by activating
SETLKOUT input, or internally by a trip, that is with the setting AutoLock = On and the setting
TripLockout=On, then also the trip output is set latched.
The lockout can manually be reset after checking the primary fault by activating the reset lockout
input RSTLKOUT. Note that the activation of the RSTLKOUT input will initiate a short pulse of 3 ms.
A new reset needs a new activation of the RSTLKOUT input.
14.1.3.3
Example of directional data
An example how to connect the directional data from different application functions to the trip function
is given below, see
292
Figure
145. Signals that are not used are dimmed.
TMAGAPC
TMAGAPC
EF4PTOC TRIP
Tripping logic SMPPTRC is used for a simple tripping application
Figure
146:
© 2017 - 2023 Hitachi Energy. All rights reserved
SMPPTRC
SMPPTRC
I2P
I2P
I2P
TRIP
TRIP
TRIP
U2P
U2P
U2P
TRN
TRN
TRN
BLOCK
BLOCK
BLOCK
CLLKOUT
CLLKOUT
CLLKOUT
TRINALL
TRINALL
TRINALL
START
START
START
TRINL1
TRINL1
TRINL1
STL1
STL1
STL1
TRINL2
TRINL2
TRINL2
STL2
STL2
STL2
TRINN
TRINN
TRINN
STN
STN
STN
SETLKOUT
SETLKOUT
SETLKOUT
FW
FW
FW
RSTLKOUT
RSTLKOUT
RSTLKOUT
REV
REV
REV
STDIR
STDIR
STDIR
FLTIL1MAG
FLTIL1MAG
FLTIL1MAG
RSTFLTUI
RSTFLTUI
RSTFLTUI
FLTIL1ANG
FLTIL1ANG
FLTIL1ANG
FLTIL2MAG
FLTIL2MAG
FLTIL2MAG
FLTIL2ANG
FLTIL2ANG
FLTIL2ANG
FLTINMAG
FLTINMAG
FLTINMAG
FLTINANG
FLTINANG
FLTINANG
FLTUL1MAG
FLTUL1MAG
FLTUL1MAG
FLTUL1ANG
FLTUL1ANG
FLTUL1ANG
FLTUL2MAG
FLTUL2MAG
FLTUL2MAG
FLTUL2ANG
FLTUL2ANG
FLTUL2ANG
FLTUNMAG
FLTUNMAG
FLTUNMAG
FLTUNANG
FLTUNANG
FLTUNANG
1MRK506375-UEN Rev. N
M14828-18 v7
GUID-08AC09AB-2B2F-4095-B06E-1171CF225869 v4
Railway application RER670
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer670

Table of Contents