Hitachi Relion 670 Series Applications Manual page 344

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 15
Monitoring
1  phase 
supply
V = V
IEC17000212 V1 EN-US
Figure 166:
The SystemType setting is set as 2Phase to operate the RWRFLO for single phase traction supply
systems. The analog input needed for this functionality is catenary voltage and catenary current.
The functionality provides the mentioned accuracies only for single track systems. For paralleling
tracks, the below reasons effects increases the in-accuracies in the algorithm:
The impedance of the line will be changed due to paralleling
The effect of remote in-feed to the fault through hair pin connections at paralleling points
TSS
R
IEC17000216 V1 EN-US
Figure 167:
The effect of mutual impedance between the parallel lines changes the reactive impedance of
the line.
Application of BT based single-phase traction supply using SystemType =
BTCatenary
The fault location in BT based single-phase supply system can be estimated by setting the function
as BTCatenary.
In this system type, the function needs to be provided with loop impedances (resistance and
reactance) of each section. In this system, the line lengths are less, hence it is recommended to use
the minimum number of sections possible.
PHSELL2 should be connected to FALSE.
The line section details required to provide is the loop impedance (LineLengthx, R1Lx, and X1Lx,
where x is section number).
338
Booster 
transformer
I
c
TSS
RER
c
I = I
c
Classical single phase feeding diagram
A
B
Local in 
feed
Fault
Paralleling points diagram
© 2017 - 2023 Hitachi Energy. All rights reserved
transformer
Aerial return conductor
Catenary
Locomotive
Paralleling 
post
A
B
Remote in 
feed
1MRK506375-UEN Rev. N
Booster 
IEC17000212-1-en.vsdx
Paralleling 
post
IEC17000216-1-en.vsdx
Railway application RER670
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer670

Table of Contents