Section 12
Control
BC12CLTR (sect.1)
DCCLTR (A1A2)
DCCLTR (B1B2)
BC12CLTR (sect.2)
VPBC12TR (sect.1)
VPDCTR (A1A2)
VPDCTR (B1B2)
VPBC12TR (sect.2)
BC17OPTR (sect.1)
DCOPTR (A1A2)
BC17OPTR (sect.2)
BC17CLTR (sect.1)
DCCLTR (A1A2)
BC17CLTR (sect.2)
VPBC17TR (sect.1)
VPDCTR (A1A2)
VPBC17TR (sect.2)
BC27OPTR (sect.1)
DCOPTR (B1B2)
BC27OPTR (sect.2)
BC27CLTR (sect.1)
DCCLTR (B1B2)
BC27CLTR (sect.2)
VPBC27TR (sect.1)
VPDCTR (B1B2)
VPBC27TR (sect.2)
EXDU_BC (sect.1)
EXDU_DC (A1A2)
EXDU_DC (B1B2)
EXDU_BC (sect.2)
IEC04000480 V1 EN-US
Figure 95:
For a line bay in section 2, the same conditions as above are valid by changing section 1 to section 2
and vice versa.
12.4.2.4
Configuration setting
If there is no bypass busbar and therefore no QB7 disconnector, then the interlocking for QB7 is not
used. The states for QB7, QC71, BB7_D, BC_17, BC_27 are set to open by setting the appropriate
module inputs as follows. In the functional block diagram, 0 and 1 are designated 0=FALSE and
1=TRUE:
QB7_OP = 1
QB7_CL = 0
QC71_OP = 1
QC71_CL = 0
240
&
>1
&
>1
&
Signals to a line bay in section 1 from the bus-coupler bays in each section
© 2017 - 2023 Hitachi Energy. All rights reserved
BC_12_CL
>1
VP_BC_12
&
BC_17_OP
&
BC_17_CL
>1
VP_BC_17
&
BC_27_OP
&
BC_27_CL
>1
VP_BC_27
&
EXDU_BC
&
en04000480.vsd
1MRK506375-UEN Rev. N
M13560-108 v4
Railway application RER670
Application manual