1MRK506375-UEN Rev. N
Event reporting mode
If EventRepMode = SeqOfEvent, all GI and spontaneous events will be delivered in the order they
were generated by BSW. The most recent value is the latest value delivered. All GI data from a
single block will come from the same cycle.
If EventRepMode = HiPriSpont, spontaneous events will be delivered prior to GI event. To prevent
old GI data from being delivered after a new spontaneous event, the pending GI event is modified to
contain the same value as the spontaneous event. As a result, the GI dataset is not time-correlated.
18.6.2.2
Settings from PCM600
I103USEDEF
For each input of the I103USEDEF function there is a setting for the information number of the
connected signal. The information number can be set to any value between 0 and 255. To get proper
operation of the sequence of events the event masks in the event function is to be set to
ON_CHANGE. For single-command signals, the event mask is to be set to ON_SET.
In addition there is a setting on each event block for function type. Refer to description of the Main
Function type set on the local HMI.
Commands
As for the commands defined in the protocol there is a dedicated function block with eight output
signals. Use PCM600 to configure these signals. To realize the BlockOfInformation command, which
is operated from the local HMI, the output BLKINFO on the IEC command function block ICOM has
to be connected to an input on an event function block. This input must have the information number
20 (monitor direction blocked) according to the standard.
Disturbance Recordings
For each input of the Disturbance recorder function there is a setting for the information number of
the connected signal. The function type and the information number can be set to any value between
0 and 255. To get INF and FUN for the recorded binary signals, there are parameters on the
disturbance recorder for each input. The user must set these parameters to whatever he connects to
the corresponding input.
Refer to description of Main Function type set on the local HMI.
Recorded analog channels are sent with ASDU26 and ASDU31. One information element in these
ASDUs is called ACC, and it indicates the actual channel to be processed. The channels on
disturbance recorder are sent with an ACC as shown in Table 49.
Table 49:
DRA#-Input
1
2
3
4
5
6
7
8
9
10
11
Table continues on next page
Railway application RER670
Application manual
Channels on disturbance recorder sent with a given ACC
© 2017 - 2023 Hitachi Energy. All rights reserved
ACC
1
2
3
4
5
6
7
8
64
65
66
Station communication
GUID-A41170D6-2846-4E5E-8B7F-85B53D4EF6B6 v1
IEC 60870-5-103 meaning
IL1
IL2
IL3
IN
UL1
UL2
UL3
UN
Private range
Private range
Private range
Section 18
M17109-132 v2
M17109-138 v2
M17109-141 v8
383