Hitachi Relion 670 Series Applications Manual page 278

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 12
Control
12.9.1
Identification
Function description
Single point generic control 8 signals
12.9.2
Application
The Single point generic control 8 signals (SPC8GAPC) function block is a collection of 8 single point
commands that can be used for direct commands for example reset of LED's or putting IED in
"ChangeLock" state from remote. In this way, simple commands can be sent directly to the IED
outputs, without confirmation. Confirmation (status) of the result of the commands is supposed to be
achieved by other means, such as binary inputs and SPGAPC function blocks.
12.9.3
Setting guidelines
The parameters for the single point generic control 8 signals (SPC8GAPC) function are set via the
local HMI or PCM600.
Operation: turning the function operation On/Off.
There are two settings for every command output (totally 8):
PulseModex: decides if the command signal for output x is Latched (steady) or Pulsed.
tPulsex: if PulseModex is set to Pulsed, then tPulsex will set the length of the pulse (in seconds).
12.10
AutomationBits, command function for DNP3.0
AUTOBITS
12.10.1
Identification
Function description
AutomationBits, command function for
12.10.2
Application
Automation bits, command function for DNP3 (AUTOBITS) is used within PCM600 in order to get into
the configuration the commands coming through the DNP3.0 protocol. The AUTOBITS function plays
the same role as functions GOOSEBINRCV (for IEC 61850) and MULTICMDRCV (for LON).
AUTOBITS function block have 32 individual outputs which each can be mapped as a Binary Output
point in DNP3. The output is operated by a "Object 12" in DNP3. This object contains parameters for
control-code, count, on-time and off-time. To operate an AUTOBITS output point, send a control-code
of latch-On, latch-Off, pulse-On, pulse-Off, Trip or Close. The remaining parameters are regarded as
272
IEC 61850
identification
SPC8GAPC
PSTO is the universal operator place selector for all control functions. Even if PSTO can
be configured to allow LOCAL or ALL operator positions, the only functional position
usable with the SPC8GAPC function block is REMOTE.
IEC 61850
identification
AUTOBITS
DNP3
© 2017 - 2023 Hitachi Energy. All rights reserved
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
GUID-C3BB63F5-F0E7-4B00-AF0F-917ECF87B016 v4
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Railway application RER670
1MRK506375-UEN Rev. N
SEMOD176456-2 v3
SEMOD176511-4 v7
SEMOD176518-4 v7
SEMOD158589-1 v3
SEMOD158637-5 v4
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer670

Table of Contents