ABB i-bus KNX Product Manual page 20

Room thermostat fan coil with display
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus KNX
© 2009 Busch-Jaeger Elektro GmbH – A Company of the ABB Group
Commissioning
Control value at temp. measuring error
Options:
- Final value
- 0 %
- 10 %
- 20 %
- 30 %
- 40 %
- 50 %
- 60 %
- 70 %
- 80 %
- 90 %
- 100 %
In case of error the device output uses the specified value to run an
emergency function.
Monitoring time exterior temperature (0 – inactive, min)
Options:
- 0 / 1 / ... / 10 / ... / 60
If the "Monitoring temperature measurement" parameter is set to "yes",
the time within which the external temperature sensor must send a message
to the bus is set here.
Monitoring time exterior temperature (0 – inactive, min)
Options:
- 0 / 1 / .../ 10 / ... / 60
If the "Monitoring temperature measurement" parameter is set to "yes",
the time within which the outside temperature sensor must send a message
to the bus is set here.
Offset for ext. temp. meas.
(measured value changes by (-128..127)x0,1 K)
Options:
- -128
- ...
- 0
- ...
- 127
Value range –128..127 corresponds to –12.8K..12.7K
The measured outside temperature can be adjusted with this parameter.
This means that if the outside temperature is falsified by heat or cooling
effects at the temperature sensor, the measured value can be adjusted
up or down.