Special Operating States - ABB i-bus KNX Product Manual

Room thermostat fan coil with display
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus KNX
3.4

Special operating states

© 2009 Busch-Jaeger Elektro GmbH – A Company of the ABB Group
Commissioning
Behaviour after reset
The behaviour after reset can be set for the operating mode, the operating
type and the fan stage.
Heating, cooling and the state of the object "switching heating/cooling" can
be selected for the operating mode. When it is set to "depending on object
"switching heating/cooling"", the object state is queried via the bus when
switching on or after a reset.
Comfort mode is default after reset, however Standby, Night mode or
Frost/Heat Protection can also be selected.
The active fan stage after reset can be stage 1, 2 or 3. If no stage is to be
active after reset, select the setting "Off". The setting "Automatic" switches
on the fan stage in accordance with the current control value.
81

Advertisement

Table of Contents
loading

Table of Contents