3.2.14 Parameter window
"FanCoil heating"
© 2009 Busch-Jaeger Elektro GmbH – A Company of the ABB Group
Commissioning
Stage limit in night mode
Options:
- No limit
- Fan Off
- Stage 1
- Stage 2
If the device is used in an environment such as a hotel room, it may be
desirable to limit the fan stages during the night to reduce the noise.
The parameter "Stage limit in night mode" is used for this. If the parameter
is set to stage 1, the fan will not use more that the first stage when night
mode is enabled. This will apply even if the transmitted control value
requests a higher fan stage.
Automatic return from manual adjustment (0 - inactive, min)
Options:
- 0 / 1 / 2 / ... / 60
If "Manual stage switching" was performed by the user, this action can
be reset via onsite operation of the ambient temperature controller.
However, a time can also be input after which the ambient temperature
cancels the "Manual stage switching" and switches back to automatic
stage switching mode.
This parameter is only available if the "Heating" or "Heat and cool" control
functions are used and the heating control type is set to "FanCoil".