Commissioning
Heating setpoint comfort mode
Options:
- 16.0 °C
- 16.5 °C
- ...
- 21.0 °C
- ...
- 31.0 °C
The "Heating setpoint comfort mode" specifies the individual comfort
temperature for the heating mode. This parameter is only available if
the "Heating" or "Heat and cool" control functions are used, in which the
setpoints "Dependent setpoints" (tab "Setpoints general") have been
selected and the reference of the base setpoint has been set to "Base
setpoint heating".
Heating setpoint reduction standby
Options:
- 0.5 K
- 1.0 K
- ...
- 2 K
- ...
- 8.0 K
The setting "Heating setpoint reduction standby" allows you to specify
the number of degrees Kelvin that the comfort temperature is lowered
during standby operation.
This parameter is only available if the parameter "Selection of base setpoint"
(tab "Setpoint general") is set to "Dependent setpoints".