4.1.1
Operating mode
switching 1 bit
4.1.2
Operating mode
switching 1 byte
© 2009 Busch-Jaeger Elektro GmbH – A Company of the ABB Group
The frost/heat protection has the top priority, i.e. in this case switching
to a different operating mode is disabled. Frost/heat protection must be
disabled first, e.g. by closing an open window. Night mode has the next
higher priority, followed by comfort mode. If none of the above three
operating modes are enabled, the ambient temperature controller is in
standby mode.
1-Byte
Betriebsarten-
umschaltung
Komfort-
Betrieb
Standby-
Betrieb
Nacht-
Betrieb
Frost-/Hitze-
schutz-
Betrieb
When switching operating mode via 1 byte two 1-byte communication
objects are available.
The two 1-byte communication objects have different behaviour when
receiving a telegram. An object evaluates received telegrams as "normal"
(operating mode switching). This means, for example, if a comfort telegram
is received, the room thermostat switches to comfort mode. If a night
telegram is received, the ambient temperature controller switches to night
mode. This object is controlled, for example, by time switches.
1-Byte
Betriebsarten-
umschaltung OMO
Auto
Komfort-
Betrieb
Standby-
Betrieb
Betriebsart
Nacht-
Betrieb
Frost-/Hitze-
schutz-
Betrieb