Commissioning
Setpoint frost protection
Options:
- 0 °C
- 1 °C
- ...
- 7 °C
- ...
- 15 °C
The setpoint for frost protection is the temperature that may not be
undershot during the frost protection mode. If the current temperature
undershoots the configured value, the ambient temperature controller
triggers a control value telegram that causes the relevant heating actuator
to heat up the room to prevent damage to the heating system from frost-
related cooling.
This parameter is only available if the "Heating" or "Heat and cool" control
functions are used.
Setpoint heat protection
Options:
- 30.0 °C
- 30.5 °C
- ...
- ...
- 44.0 °C
- Cooling disabled
The setpoint for heat protection is the temperature that may not be overshot
during heat protection mode. If the current temperature overshoots the
configured value, the ambient temperature controller triggers a control value
telegram that causes the relevant cooling unit to cool the room to prevent
damage from heat build-up.
This parameter is only available if the "Cooling" or "Heat and cool" control
functions are used.
Note:
At the setpoint 99.9 °C is sent at "Cooling disabled".