Room thermostat fan coil with display
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

© 2009 Busch-Jaeger Elektro GmbH – A Company of the ABB Group
The second object )"operating mode switching OMO") may "overwrite"
the first temporarily. This means, for example, if a frost/heat protection
telegram is received, the ambient temperature controller switches to frost
or heat protection mode. If the frost or heat protection is reset by the receipt
of another telegram, the ambient temperature controller enables the
operating mode on the "normal" object. As a result, it is capable of noting
operating modes. This object is controlled, for example, by binary inputs
that record information from window contacts.
The following apply to both 1-byte communication objects:
0
= auto ("operating mode switching OMO" only)
1
= comfort
2
= standby
3
= night
4
= frost/heat protection
5 – 255 = not permitted