Commissioning
Cooling setpoint standby mode
Options:
- 21.0 °C
- 21.5 °C
- ...
- 25.0 °C
- ...
- 36.0 °C
"Cooling setpoint for standby mode" specifies the individual standby
temperature for cooling mode. The temperature value specified does
not depend on the specified "Cooling setpoint comfort mode".
This parameter is only available if the parameter "Selection of base setpoint"
(tab "Setpoint general") is set to "Individual setpoints".
Cooling setpoint night mode
Options:
- 23.0 °C
- 23.5 °C
- ...
- 27.0 °C
- ...
- 38.0 °C
"Cooling setpoint night mode" specifies the individual temperature during
the night for cooling mode. The temperature value specified does not
depend on the specified "Cooling setpoint comfort mode".
This parameter is only available if the parameter "Selection of base setpoint"
(tab "Setpoint general") is set to "Individual setpoints".
Minimum distance between heating setpoint and cooling setpoint
Options:
- 0.0 K
- 0.5 K
- ...
- 2 K
- ...
- 7.5 K
The comfort temperature for cooling can be adjusted with "Minimum
distance between heating and cooling". The cooling setpoint increases
for standby and night mode are based on this value.
If, for instance, with a comfort temperature (base setpoint) of 21 °C you
want to cool at 26 °C in comfort mode, you have to set a dead zone of 5 K
(see also page 95 Section 4.4.3 Minimum distance).
This parameter is only available if the parameter "Selection of base setpoint"
(tab "Setpoint general") is set to "Dependent setpoints".