Monitor display and monitor output signal

3.10.3 CA, AM terminal function selection (Pr.54 to Pr.56, Pr.158, Pr.867, Pr.869)

For signal output, two different output terminals are available: pulse train output terminal CA and analog
Pr.52
output terminal AM.
page 100
Pr.57
You can select the signals output to the terminals CA, AM.
page 109
Pr.157
Parameter
page 56
Number
Pr.159
CA terminal function
page 192
54 *
selection
Pr.611
page 109
AM terminal function
158 *
Pr.872
selection
page117
Frequency monitoring
55 *
reference
Current monitoring
56 *
reference
867
AM output filter
869
Current output filter
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 140)
* The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set
in Pr. 77 Parameter write selection.
(1) Output signal list (Pr.54, Pr.158)
• In Pr. 54, set the monitor to be output to the terminal CA (Analog output (0 to 20 mADC current output)).
• In Pr. 158, set the monitor to be output to the terminal AM (analog output (0 to 10VDC voltage output)).
• Refer to the following table and set the monitor to be output.
Types of Monitor
Output frequency
Output current
Output voltage
Frequency setting
Running speed
Converter output
voltage
Regenerative brake
duty
Electronic thermal relay
function load factor
Output current peak
value
Converter output
voltage peak value
Input power
Output power
Load meter
Reference voltage
output
Motor load factor
104
Name
Initial Value
(output
frequency)
50Hz
Rated inverter
output current
0.01s
0.02s
Pr.54 (CA)
Increments
Pr.158 (AM)
Setting
0.01Hz
1
/0.1A *
0.01A
2
0.1V
3
0.01Hz
5
1(r/min)
6
0.1V
8
9
0.1%
0.1%
10
0.01A
/0.1A *
11
0.1V
12
0.01kW
/
13
0.1kW *
0.01kW
/
14
0.1kW *
0.1%
17
21
0.1%
24
Setting Range
1
1 to 3, 5, 6, 8 to 14,
17, 21, 24, 50, 52, 53
0 to 400Hz
01160 or
0 to 500A Set the full-scale value to output
less
01800 or
0 to
more
3600A
0 to 5s
0 to 5s
Full Scale Value
Pr. 55
Displays the inverter output frequency.
Displays the inverter output current effective value.
Pr. 56
800V
Displays the inverter output voltage.
Displays the set frequency.
Pr. 55
Value of Pr. 55
Displays the motor speed.
represented in terms
(Depending on the Pr. 37 and Pr. 144 settings.
of Pr. 37 value
Refer to page 99 for details.)
800V
Displays the DC bus voltage value.
Indicates the brake duty in %.
Pr. 70
(Setting can be made only for the 01800 or
more)
Electronic thermal
Displays the motor thermal cumulative value on
relay function
the assumption that the thermal operation level is
operation level
100%.
Holds and displays the peak value of the output
Pr. 56
power monitor. (Cleared at every start)
Holds and displays the peak value of the DC bus
800V
voltage value. (Cleared at every start)
Rated inverter power
Displays the power on the inverter input side.
×
2
Rated inverter power
Displays the power on the inverter output side.
×
2
Displays the torque current in % on the
Pr. 56
assumption that the Pr. 56 setting is 100%.
Terminal CA: Outputs 20mA.
Terminal AM: Outputs 10V.
Load factor with respect to motor rated current
Monitor value = output power monitor value/rated
200%
inverter current
Description
Select the monitor output to
terminal CA.
Select the monitor output to
terminal AM.
Set the full-scale value to output
the output frequency monitor value
to terminal CA and AM.
the output current monitor value to
terminal CA and AM.
Set the output filter of terminal AM.
Adjust response level of current
output.
Description
×
100 [%]