(1) Connection diagram
⋅ The following shows the connection diagram of a typical commercial power supply switchover sequence. Sink
logic, Pr. 185 = "7", Pr. 192 = "17", Pr. 193 = "18", Pr. 194 = "19"
MCCB
MC1
R/L1
S/L2
T/L3
R1/L11
S1/L21
Inverter start
(forward rotation)
STF
Inverter/commercial
power-supply switchover
CS
MRS
Operation interlock
*3
External
JOG(OH)
thermal reset
RES
PC
10
Frequency
2
setting signal
5
Commercial power supply switchover sequence
connection diagram
CAUTION
⋅ Use the commercial power supply switchover function in external operation mode. Be sure to connect the other power
supply since the function is not performed normally unless the connection terminals R1/L11, S1/L21 are not connected to
the other power supply (power supply that does not pass MC1).
⋅ Be sure to provide mechanical interlocks for MC2 and MC3.
⋅ Operations of magnetic contactors (MC1, MC2, MC3)
Magnetic
Contactor
Between power supply and
MC1
inverter input
Between power supply and
MC2
motor
Between inverter output and
MC3
motor
MC2
External
thermal relay
MC3
U
V
W
*1
MC
(MC1)IPF
1
MC3
*1
MC
(MC2)OL
2
MC2
*1
MC
(MC3)FU
3
SE
Installation Place
Special operation and frequency setting
*1
Take caution for the capacity of the sequence output
terminal.
The used terminal changes depending on the setting of Pr.
190 to Pr. 196 (output terminal function selection).
Output Terminal Capacity
IM
Inverter open collector output
(RUN, SU, IPF, OL, FU)
Inverter relay output (A1-C1,
B1-C1, A2-B2, B2-C2)
Relay output option (FR-A7AR)
*2
24VDC
*2
When connecting a DC power supply, insert a protective
diode. When connecting an AC power supply, connect a
relay output option (FR-A7AR) and use a contact output.
*3
The used terminal changes depending on the setting of Pr.
180 to Pr. 189 (input terminal function selection).
Operation ( : Shorted, ×: Open)
Commercial
During Inverter
Power Supply
Operation
Operation
×
Output Terminal
Permissble Load
24VDC 0.1A
230VAC 0.3A
30VDC 0.3A
At an Inverter
Alarm Occurrence
×
(Shorted by reset)
×
(Can be selected
×
using Pr. 138, always
open when external
thermal relay is on)
×
3
193