Function assignment of external
terminal and control
Setting
Signal
Positive
Negative
Name
Logic
Logic
14
114
FDN
15
115
FUP
16
116
RL
17
MC1
18
MC2
19
MC3
25
125
FAN
26
126
FIN
45
145
RUN3
46
146
Y46
47
147
PID
64
164
Y64
70
170
SLEEP
71
RO1
72
RO2
73
RO3
74
RO4
75
RIO1
76
RIO2
77
RIO3
78
RIO4
90
190
Y90
91
191
Y91
92
192
Y92
92
Function
Output when the feedback value falls below
PID lower limit
the lower limit of PID control.
Output when the feedback value rises above
PID upper limit
the upper limit of PID control
PID forward/reverse
Output when forward rotation is performed in
rotation output
PID control.
Commercial power-
supply switchover MC1
Used when the commercial power
Commercial power-
supply-inverter switchover function is
supply switchover MC2
used.
Commercial power-
supply switchover MC3
Fan fault output
Output at the time of a fan fault.
Output when the heatsink temperature
Heatsink overheat
reaches about 85% of the heatsink overheat
pre-alarm
protection providing temperature.
During inverter
Output when the inverter running and start
running and start
commands are on.
command is on
During deceleration at
occurrence of power
Output when the power failure-time
failure (retained until
deceleration function is executed.
release)
During PID control
Output during PID control.
activated
During retry
Output during retry processing.
PID output
Output when the PID output interruption
interruption
function is executed.
Commercial-power
supply side motor 1
connection RO1
Commercial-power
supply side motor 2
connection RO2
Commercial-power
supply side motor 3
connection RO3
Commercial-power
Used when using advanced PID control
supply side motor 4
(pump function).
connection RO4
Inverter side motor 1
connection RIO1
Inverter side motor 2
connection RIO2
Inverter side motor 3
connection RIO3
Inverter side motor 4
connection RIO4
Output when any of the control circuit
capacitor, main circuit capacitor and inrush
Life alarm
current limit circuit or the cooling fan
approaches the end of its service life.
Alarm output 3
Output when an error occurs due to the circuit
(power-off signal)
failure or connection alarm of the inverter.
Energy saving
Turned on and off alternately every time the
average value
power saving average value is updated
updated timing
when the power saving monitor is used.
Operation
Related
Refer
Parameters
to Page
Pr. 127 to Pr.
134, Pr. 575 to
184
Pr. 577
Pr. 135 to Pr. 139,
192
Pr. 159
Pr. 244
210
235
93
Pr. 261 to Pr. 266
112
Pr. 127 to Pr.
134, Pr. 575 to
184
Pr. 577
Pr. 65 to Pr. 69
114
Pr. 127 to Pr.
134, Pr. 575 to
184
Pr. 577
Pr. 575 to Pr.
197
591
Pr. 255 to Pr. 259
211
94
Pr. 52, Pr. 54,
Pr. 158, Pr. 891
119
to Pr. 899