Mitsubishi Electric F700 Instruction Manual page 257

Hide thumbs Also See for F700:
Table of Contents

Advertisement

Common specifications
Protective/warning function
LD
Ambient
SLD
temperature
(initial setting)
Ambient humidity
Storage temperature
*3
Atmosphere
Altitude, vibration
*1
Can be displayed only on the operation panel (FR-DU07).
*2
Can be displayed only on the parameter unit (FR-PU04).
*3
Temperature applicable for a short period in transit, etc.
*4
Only the 01800 or more functions.
250
Overcurrent during acceleration, overcurrent during constant speed, overcurrent during
deceleration, overvoltage during acceleration, overvoltage during constant speed, overvoltage
during deceleration, inverter protection thermal operation, motor protection thermal operation,
heatsink overheat, instantaneous power failure occurrence, undervoltage, input phase failure,
motor overload, output side earth (ground) fault overcurrent, output phase failure, external
thermal relay operation, PTC thermistor operation, option alarm, parameter error, PU
disconnection, retry count excess, CPU alarm, operation panel power supply short circuit,
24VDC power output short circuit, output current detection value excess, inrush resistance
overheat, communication alarm (inverter), analog input alarm, internal circuit alarm (15V
power supply), fan fault, overcurrent stall prevention, overvoltage stall prevention, electronic
thermal relay function prealarm, PU stop, maintenance timer alarm
detection
, parameter write error, copy operation error, operation panel lock, parameter copy
*4
-10°C to +50°C (non-freezing)
-10°C to +40°C (non-freezing)
90%RH or less (non-condensing)
-20°C to +65°C
Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt etc.)
Maximum 1000m above sea level for standard operation. After that derate by 3% for every
extra 500m up to 2500m (92%) 5.9m/s2 or less (conforming to JIS C 0040)
, brake transistor alarm
*1