3.23 All parameter clear

POINT
· Set "1" in ALLC parameter clear to initialize all parameters. (Parameters are not cleared when "1" is set in Pr. 77
Parameter write selection.)
1.
Screen at powering on
The monitor display appears.
2.
Press
to choose the PU operation
mode.
3.
Press
to choose the parameter
setting mode.
4.
Turn
until
clear) appears.
5.
Press
to read the currently set
value.
"
"(initial value) appears.
6.
Turn
clockwise to change it to
the setting value of " ".
7.
Press
to set.
Setting
0
Not executed.
1
All parameters return to the initial values. *
* Pr.75, Pr.171 to Pr.174, Pr.255 to Pr.258, Pr.343, Pr.496, Pr.497, Pr.503, Pr.888, Pr.889 are not cleared.
and
The inverter is not in the PU operation mode. Press
from step 6 again.
Operation
(all parameter
· Press
to read another parameter.
· Press
to show the setting again.
· Press
twice to show the next parameter.
Description
are displayed alternately ... Why?
Display
PU indication is lit.
The parameter
number read
previously appears.
Flicker ··· Parameter setting complete!!
to lit
All parameter clear
, then carry out operation