Mitsubishi Electric F700 Instruction Manual page 216

Hide thumbs Also See for F700:
Table of Contents

Advertisement

(2) To detect the regeneration status during deceleration faster (Pr.884)
⋅ As the regeneration avoidance function cannot respond to an abrupt voltage change by detection of the bus
voltage level, the ratio of bus voltage change is detected to stop deceleration if the bus voltage is less than Pr.
883 Regeneration avoidance operation level.
Set that detectable bus voltage change ratio to Pr. 884 as detection sensitivity.
Increasing the setting raises the detection sensitivity
CAUTION
Too small setting (low detection sensitivity) will disable detection, and too large setting will turn on the regeneration avoidance
function if the bus voltage is varied by an input power change, etc.
Restriction level
Output frequency (Hz)
Pr.885
(4) Regeneration avoidance function adjustment (Pr.886)
⋅ If the frequency becomes instable during regeneration avoidance operation, decrease the setting of Pr. 886
Regeneration avoidance voltage gain. Reversely, if sudden regeneration causes an overvoltage alarm, increase
the setting.
⋅ When the load inertia of the motor is large, decrease the Pr. 886 setting.
CAUTION
⋅ When regeneration avoidance operation is performed,
⋅ When regeneration avoidance operation is performed, stall prevention is also activated at the same time.
⋅ The regeneration avoidance function cannot shorten the actual deceleration time taken to stop the motor. The actual
deceleration time depends on the regeneration capability. When shortening the deceleration time, consider using the
regeneration unit (BU, FR-BU, MT-BU5, FR-CV, FR-HC, MT-HC).
⋅ When using the regeneration unit (BU, FR-BU, MT-BU5, FR-CV, FR-HC, MT-HC), set Pr. 882 to "0 (initial value)"
(regeneration avoidance function invalid).
⋅ When regeneration avoidance operation is performed, the OL signal output item of Pr. 156 also becomes the target of
(overvoltage stall). Pr. 157 OL signal output timer also becomes the target of
♦ Parameters referred to ♦
Pr.1 Maximum frequency
Refer to page 62
Pr. 8 Deceleration time
Refer to page 74
Pr.22 Stall prevention operation level
(3) Limit the output frequency (Pr.885)
You can limit the output frequency compensated for (increased)
by the regeneration avoidance function.
⋅ The frequency is limited to the output frequency (frequency prior
to regeneration avoidance operation) + Pr. 885 Regeneration
avoidance compensation frequency limit value during acceleration
or constant speed. If the regeneration avoidance frequency
exceeds the limit value during deceleration, the limit value is
Pr.885/2
held until the output frequency falls to 1/2 of Pr. 885.
Time
⋅ When the regeneration avoidance frequency has reached Pr. 1
Maximum frequency, it is limited to the maximum frequency.
⋅ Pr. 885 is set to "9999", the frequency setting is invalid.
(overvoltage stall) is displayed and the OL signal is output.
Refer to page 56
Special operation and frequency setting
(overvoltage stall).
3
209