Mitsubishi Electric F700 Instruction Manual page 93

Hide thumbs Also See for F700:
Table of Contents

Advertisement

Function assignment of external
terminal and control
Signal
Setting
Name
Pr.59 = 0 (initial value)
2
RH
Pr.59 = 1, 2
3
RT
Second function selection
4
AU
Terminal 4 input selection
5
JOG
Jog operation selection
Selection of automatic restart after instantaneous power failure,
6
CS
flying start
7
OH
External thermal relay input
8
REX
15 speed selection (combination with three speeds RL, RM, RH)
10
X10
Inverter operation enable signal (FR-HC, MT-HC, FR-CV connection) Pr.30
11
X11
FR-HC or MT-HC connection, instantaneous power failure detection
12
X12
PU operation external interlock
13
X13
External DC injection brake operation start
14
X14
PID control valid terminal
16
X16
PU-external operation switchover
24
MRS
Output stop
25
STOP
Start self-holding selection
37
X37
Traverse function selection
Forward rotation command
60
STF
(assigned to STF terminal (Pr. 178) only)
Reverse rotation command
61
STR
(assigned to STR terminal (Pr. 179) only)
62
RES
Inverter reset
63
PTC
PTC thermistor input (assigned to AU terminal (Pr. 184) only)
64
X64
PID forward/reverse action switchover
65
X65
PU-NET operation switching
66
X66
External/NET operation switchover
67
X67
Command source switchover
9999
No function
*1
When Pr. 59 Remote function selection = "1 or 2", the functions of the RL, RM and RH signals change as listed above.
*2
The OH signal turns on when the relay contact "opens".
CAUTION
⋅ Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other functions.
Please make setting after confirming the function of each terminal.
⋅ One function can be assigned to two or more terminals. In this case, the terminal inputs are ORed.
⋅ The priorities of the speed commands are in order of jog, multi-speed setting (RH, RM, RL, REX) and PID (X14).
⋅ When the X10 signal (FR-HC, FR-CV connection - inverter operation enable signal) is not set or when the PU operation
external interlock (X12) signal is not assigned at the Pr. 79 Operation mode selection setting of "7", the MRS signal shares this
function.
⋅ Use common terminals to assign multi-speeds (speed 7) and remote setting. They cannot be set individually.
(Common terminals are used since these functions are designed for speed setting and need not be set at the same time.)
(2) Response time of each signal
⋅ The response time of the X10 signal is within 2ms. However, when the X10 signal is not assigned at the Pr. 30
Regenerative function selection setting of "2" (FR-HC/MT-HC/FR-CV connection), the response time of the MRS
signal is within 2ms.
Pr. 17 MRS input selection is made invalid.
MRS
Pr.30
Setting
Assignment
×
2
×
Other than 2
86
Function
High-speed operation command
Remote setting (acceleration)
*1
*2
X10
Response Time
Assignment
MRS
×
Within 2ms
Within 20ms
×
Within 20ms
Within 20ms
Related Parameters
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 59
Pr.44 to Pr.51
Pr.267
Pr. 15, Pr. 16
Pr.57, Pr.58, Pr.162 to
Pr.165, Pr.611
Pr. 9
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr.232 to Pr.239
Pr.30
Pr. 79
Pr.11, Pr.12
Pr.127 to Pr.134, Pr.575 to
Pr.577
Pr.79, Pr.340
Pr. 17
Pr. 592 to Pr. 597
Pr. 9
Pr.127 to Pr.134, Pr.5
Pr.79, Pr.340
Pr.79, Pr.340
Pr.338, Pr.339
Pr. 17
X10
Invalid
Within 2ms
Within 2ms
Valid
Valid
Valid
Refer to
Page
67
72
53, 56, 64,
74, 78, 95
125
69
109
78
67
83
83
142
81
184
148
87
89
206
89
89
78
184
150
150
151