Setting The Address - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

4.5.11.4

Setting the address

Valid addresses: 1 ... 125
Procedure
Proceed as follows to set the PROFIBUS address:
1. Set the address using one of the subsequently listed options:
– Via the address switch
– On an operator panel via p0918
– With STARTER or Startdrive
2. Switch off the inverter supply voltage.
3. Wait until all LEDs on the inverter go dark.
4. Switch on the inverter supply voltage again.
Your settings become active after switching on.
You set the PROFIBUS address.
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Overview of the interfaces (Page 109)
After you have changed the address in STARTER, select the button "RAM to ROM"
.
4.5 Connecting the interfaces for the inverter control
You have the following options for setting the PROFI‐
BUS address:
● Using the address switch on the Control Unit:
The address switch has priority over the other
settings.
● With the parameter p0918 (factory setting:
p0918 = 126):
It is only possible to change p0918 if an invalid
address is set in the address switch.
● With STARTER or Startdrive:
Setting is only possible if an invalid address is set
in the address switch.
Installing
143