Siemens SINAMICS G120 Operating Instructions Manual page 292

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Advanced commissioning
6.21 Cascade control
Parameter
r2379
p2380
p2381
p2382
p2383
p2384
p2385
p2386
p2387
For more information, see the parameter descriptions and function diagram 7036 in the List
Manual.
292
Description
Cascade control - status word
.00
1 signal = start uncontrolled M1 motor
.01
1 signal = start uncontrolled M2 motor
.02
1 signal = start uncontrolled M3 motor
.03
1 signal = activate motor
.04
1 signal = activation/deactivation active
.05
1 signal = all motors active
.06
1 signal = automatic replacement not possible
.07
1 signal = alarm active
Cascade control - operating hours (factory setting: 0 h)
[00]
M1 motor
[01]
M2 motor
[02]
M3 motor
Cascade control - maximum time for continuous mode (factory setting: 24 h)
Time limit for continuous uninterrupted operation of uncontrolled motors
Cascade control - absolute operating time limit (factory setting: 24 h)
Limit for the total operating time of the uncontrolled motors
Cascade control - deactivation sequence (factory setting: 0)
0:
Normal stop
1:
Sequential stop:
For OFF1, the inverter deactivates the motors in the following sequence:
M3 → M2 → M1 → controlled motor
p2387 is the time between the deactivations.
Cascade control - motor switch-on delay (factory setting: 0 s)
Cascade control - stop time activation speed (factory setting: 0 s)
Cascade control - motor deactivation delay (factory setting: 0 s)
Cascade control - stop time deactivation speed (factory setting: 0 s)
See p2383
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE