General Technical Data, Pm250 - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

10.7.2

General technical data, PM250

Property
Line voltage
Output voltage
Input frequency
Output frequency
Power factor λ
Inrush current
Pulse frequency (factory set‐
ting)
Electromagnetic compatibili‐
ty
Braking methods
Degree of protection
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Version
3-phase 380 ... 480 VAC ± 10%
3-phase 0 VAC ... input voltage x 0.87 (max.)
50 Hz ... 60 Hz, ± 3 Hz
0 ... 550 Hz, depending on the control mode
0.9
< LO base load input current
4 kHz
The pulse frequency can be adjusted up to 16 kHz in 2 kHz steps. The higher the pulse
frequency, the lower the available output current.
Restrictions for special ambient conditions (Page 510)
The devices comply with EN 61800-3: 2004 suitable for Category C2 and C3 environments.
DC braking, energy recovery (up to 100% of the output power)
IP20 built-in devices (they must be installed in a switch cabinet)
10.7 Technical data, PM250 Power Module
Technical data
505