Siemens SINAMICS G120 Operating Instructions Manual page 161

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

When selecting an application class, the inverter assigns the motor control with the appropriate
default settings:
Depending on the particular Power Module, the inverter skips selecting the application
class. If the BOP-2 does not display step DRV APPL, then continue commissioning as
described under "Expert".
Select the suitable application class
When selecting an application class, the inverter assigns the appropriate settings to the motor
control.
Application class
Properties
● Typical settling time after a speed change:
● Typical settling time after a load surge: 500 ms
● Standard Drive Control is suitable for the
● Standard Drive Control is insensitive with
Application exam‐
● Pumps, fans, and compressors with flow
ples
Power Modules
that can be operat‐
ed
Max. output fre‐
quency
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Standard Drive Control (Page 162)
Dynamic Drive Control (Page 164)
Start quick commissioning and select the application class (Page 154)
Standard Drive Control
100 ms ... 200 ms
following requirements:
Motor power ratings < 45 kW
Ramp-up time 0 → rated speed
(depending on the motor power rating):
1 s (0.1 kW) ... 10 s (45 kW)
Applications with increasing load torque
without load surges
respect to imprecise setting of the motor data
characteristic
PM240‑2, PM240P-2
550 Hz
5.4 Quick commissioning using the BOP-2 operator panel
● Typical settling time after a speed change:
< 100 ms
● Typical settling time after a load surge: 200 ms
● Dynamic Drive Control controls and limits the
motor torque
● Torque accuracy that can be achieved: ± 5% for
15 % ... 100 % of the rated speed
● We recommend Dynamic Drive Control for the
following applications:
Motor power ratings > 11 kW
For load surges 10 % ... >100 % of the rated
motor torque
● Dynamic Drive Control is necessary for a ramp-
up time 0 → rated speed (dependent on the rated
motor power): < 1 s (0.1 kW) ... < 10 s (132 kW).
● Pumps and compressors with displacement
machines
PM240‑2, PM240P-2
240 Hz
Commissioning
Dynamic Drive Control
PM330
150 Hz
161