Siemens SINAMICS G120 Operating Instructions Manual page 98

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Installing
4.4 Connecting the line supply and motor
In addition, for frame sizes FSD and FSE, release the two terminal screws on the connections
for the motor and remove the dummy plug.
For frame size FSF you must breakout the openings from the connection cover for the power
connections. Use side cutters or a fine saw blade.
Figure 4-22
You must re-attach the connection covers in order to re-establish the touch protection of the
inverter after it has been connected up.
98
Line and motor connections
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE