Siemens SINAMICS G120 Operating Instructions Manual page 475

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Article No.
Recommended cable cross-section for 500 V
- line cable
- motor cable
3)
Recommended cable cross-section for 690 V
- line cable
- motor cable
3)
Recommended cable cross-section for 500 V
- DC link infeed (2/3 inverter power)
Recommended cable cross-section for 690 V
- DC link infeed (2/3 inverter power)
Tightening torque for line, motor, DC link, and
ground cable
Dimensions: Width x height x depth [mm]
Weight
The line supply must be capable of supplying the minimum short-circuit current so that the fuses trigger and consequential
1)
damage is avoided.
Note: If the minimum short-circuit current is not reached, then the tripping time for the fuses increases, and this may result
in consequential damage.
When semiconductor fuses are used, they must be mounted in the same higher construction as the inverter.
2)
The motor cables must be evenly distributed at both connection chambers.
3)
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
6SL3310-
1PG35-8AA0
2 x 240 mm
2 x 185 mm²
2 x 240 mm
2 x 185 mm²
2 x 185 mm
2 x 150 mm
50 Nm / 443 lbf in
801 x 1621 x 393
236 kg
10.5 Technical data, PM330 Power Module
1PG36-5AA0
3 x 185 mm
2
2
2 x 240 mm²
3 x 150 mm
2
2
2 x 240 mm²
2 x 185 mm
2
2
2 x 185 mm
2
2
50 Nm / 443 lbf in
801 x 1621 x 393
236 kg
Technical data
1PG37-2AA0
3 x 185 mm
2
2 x 240 mm²
3 x 185 mm
2
2 x 240 mm²
2 x 240 mm
2
2 x 185 mm
2
50 Nm / 443 lbf in
801 x 1621 x 393
246 kg
475