Analog Outputs - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

6.3.4

Analog outputs

Overview
Defining the analog output type
The inverter offers a series of default settings, which you can select using parameter p0776:
AO 0
AO 1
Characteristics
If you change the analog output type, then the inverter automatically selects the appropriate
scaling of the analog output. The linear scaling characteristic is defined using two points
(p0777, p0778) and (p0779, p0780).
Figure 6-5
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Current output (factory setting)
Voltage output
Current output
Current output (factory setting)
Voltage output
Current output
Examples for scaling characteristics
6.3 Adapt the default setting of the terminal strip
Define the analog output type using parameter
p0776.
You define the analog output function by intercon‐
necting parameter p0771 with a connector output
CO of your choice.
Connector outputs are marked with "CO" in the pa‐
rameter list of the List Manual.
Interconnecting signals in the converter
(Page 533).
0 mA ... +20 mA
0 V ... +10 V
+4 mA ... +20 mA
0 mA ... +20 mA
0 V ... +10 V
+4 mA ... +20 mA
Advanced commissioning
p0776[0] =
0
1
2
p0776[1] =
0
1
2
207