Siemens SINAMICS G120 Operating Instructions Manual page 490

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Technical data
10.6 Technical data, PM240-2 Power Module
Table 10-54 PM240-2, PT, Frame Size B, 3-ph. AC 380 V ... 480 V
Article number without filter
Article number with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL, class J
Power loss
Required cooling air flow
Weight without filter
Weight with filter
1) approx. 0.16 kW through the heatsink
Table 10-55 PM240-2, IP20, Frame Size C, 3-ph. AC 380 V ... 480 V
Article number without filter
Article number with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL, class J
Power loss
Required cooling air flow
Weight without filter
Weight with filter
490
6SL3211-1PE21-8UL0
6SL3211-1PE21-8AL0
7.5 kW
22.2 A
18.0 A
5.5 kW
19.8 A
13.7 A
3NA3812 (32 A)
35 A
0.2 kW
1)
9.2 l/s
3.6 kg
3.9 kg
6SL3210-1PE22-7UL0
6SL3210-1PE22-7AL0
11.0 kW
32.6 A
26.0 A
7.5 kW
27.0 A
18.0 A
3NA3820 (50 A)
50 A
0.3 kW
18.5 l/s
4.7 kg
5.3 kg
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
6SL3210-1PE23-3UL0
6SL3210-1PE23-3AL0
15.0 kW
39.9 A
32.0 A
11.0 kW
36.0 A
26.0 A
3NA3820 (50 A)
50 A
0.37 kW
18.5 l/s
4.8 kg
5.4 kg
Converter with the CU230P-2 Control Units

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120p

Table of Contents