Siemens SINAMICS G120 Operating Instructions Manual page 376

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Saving the settings and series commissioning
7.1 Backing up and transferring settings using a memory card
4. Select the settings as shown in the diagram and start the data backup.
5. Wait until STARTER signals that the data backup has been completed.
6. Close the screen forms.
7. Go offline.
8. Switch off the inverter power supply.
9. Wait until all LEDs on the inverter are dark.
10.Switch on the inverter power supply again.
Your settings become effective after switching on.
You have now transferred your settings from a memory card to the inverter.
Procedure with Startdrive
Proceed as follows to transfer settings from a memory card to the inverter:
1. Go online.
2. Select "Online & diagnostics".
376
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE