Siemens SIPROTEC 5 Manual page 126

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Power-System Data
5.8 Settings
Addr.
_:3844:116
Brk.wire det.
_:5581:1
_:5581:101
_:5581:102
Supv. balan. I
_:2491:1
_:2491:101
Supv. ph.seq.I
_:2551:1
_:2551:6
126
Parameter
C
CT 4:Sequence number
device
Brk.wire det.:Mode
Brk.wire det.:Mode of
blocking
Brk.wire det.:Delta value
for autoblock
Supv. balan. I:Mode
Supv. balan. I:Release
1 A @ 100 Irated 0.030 A to 35.000 A
threshold
5 A @ 100 Irated 0.15 A to 175.00 A
1 A @ 1.6 Irated
5 A @ 1.6 Irated
_:2491:102
_:2491:6
Supv. ph.seq.I:Mode
Supv. ph.seq.I:Delay
failure indication
Setting Options
1 to 2147483647
off
on
test
blocking
auto blocking
not blocking
0.004 to 5.000
off
on
test
0.001 A to 1.600 A
0.005 A to 8.000 A
Supv. balan. I:Threshold
min/max
Supv. balan. I:Delay failure
indication
off
on
test
0.00 s to 100.00 s
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Default Setting
2147483647
off
blocking
1.000
off
0.500 A
2.50 A
0.500 A
2.500 A
0
0
.
.
5
1
0
0
t
o
0
.
9
5
5
0
.
.
0
0
0
0
s
s
t
o
1
0
0
.
0
0
s
off
5.00 s