Setting Relative Time Reference
Which indications in the selected log can be displayed depends on the assignments in the DIGSI 5 infor-
²
mation routing matrix or is predefined.
You will find information about this in the chapter

Display of Indications

3.1.4
Displayed indications in DIGSI 5 and on the on-site operation panel are supplemented with the following infor-
mation:
Table 3-1
Indications in
Log for operational indications
and log for user-defined indica-
tions
DIGSI 5: Quality Indication Column
Quality
good
invalid
DIGSI 5: Additional Information Indication Column
The entries in the column for additional information are in the format Cause/Originator/Additional Cause:
Cause → What was the cause?
Originator → Who was the originator?
Additional cause → Supplementary notes
Cause
Data change
Data update
General interrogation
Cyclic
Quality change
Initiator
Maintenance
Process
Additional cause
Selection failed
invalid position
Position attained
Parameter change running
Final position attained
Impermissible mode
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Overview of additional information
DIGSI 5 Information
Time stamp (Date and time),
Relative time,
Increasing entry number,
Value,
Message number,
Quality,
Cause
Meaning
Indication is valid
Indication is invalid
Meaning
Value change in an indication
Update of indication value
General interrogation
Cyclical general inquiry
Change of the indication quality
Meaning
Maintenance
Device operation (normal)
Meaning
Selection failed
invalid position
Position attained
Parameter change running
Final position attained
Impermissible mode
3.1.5.1 General
.
Device Display Information
Time stamp (Date and time),
Value
System Functions
3.1 Indications
45