Application And Setting Notes - Siemens SIPROTEC 5 Manual

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Function-Group Types
6.5 Function-Group Type Analog Units
Table 6-8
Error Description
The input value lies outside the
given limits
Channel not connected
6.5.3.6

Application and Setting Notes

Parameter: Unit
Default setting (_:13111:103) Unit = °C
You use the setting Unit to specify which physical unit of measurement the measured values represent. The
possible setting values are listed in the settings table.
Parameter: Conversion factor
Default setting (_:13111:104) Conversion factor = 100
The Conversion factor setting allows you to set the conversion factor for the measuring transducer.
Parameter: Resolution
Default setting (_:13111:108) Resolution = 0.1
The Resolution setting is used to specify the measured value resolution.
Parameter: Range active
Default setting (_:13111:107) Range active = false
If you do not activate the Range active setting (no x in the check box), the function operates over the
range -24 mA to +24 mA. The setting of the range for the scaled value goes from a usable range of -20 mA to
+20 mA.
If you activate the Range active setting, then 4 additional settings Upper limit, Upper limit -
Sensor, Lower limit, and Lower limit - Sensor appear.
Parameter: Upper limit, Lower limit, Upper limit - Sensor and Lower limit - Sensor
Default setting (_:13111:105) Upper limit = 20.000 mA
Default setting (_:13111:109) Upper limit - Sensor = 100
Default setting (_:13111:106) Lower limit = 4.000 mA
Default setting (_:13111:110) Lower limit - Sensor = 100
If you activate the Range active setting, then 4 additional settings Upper limit, Lower limit, Upper
limit - Sensor, and Lower limit - Sensor appear. The setting Upper limit - Sensor is the
calculated measured value if the input current corresponds to the value in the Upper limit setting. The
setting Lower limit - Sensor is the calculated measured value if the input current corresponds to the
value in the Lower limit setting.
The following settings and information table shows only 1 of the 12 channels, as the setting possibilities of
the 12 channels do not differ.
178
Error Responses
Status
OK
OK
Health
Error Status
Yes
No
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017