Siemens SIPROTEC 5 Manual page 218

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Fault Recorder
7.1 Introduction to DIGSI 5
[dwflussr-161012-01.tif, 1, en_US]
Figure 7-5
In the following are the most important steps for setting the parameters for your fault recorder. A detailed
description of DIGSI 5 options can be found in the DIGSI Help.
Routing Measuring Points
You can use the Measuring-point routing matrix to route the physical inputs of a inputs of the SIPROTEC 5
device to the inputs of current and voltage measuring points.
Double-click Measuring point routing.
²
Finally, click Add. A window for selecting the phase characteristic (3-phase or 1-phase) appears.
²
Select both for the current and the voltage measuring points either the 3-phase or 1-phase characteristic.
²
Select the connection type.
²
Route the phases on the measuring points.
²
[scmes7ke-180213-01.tif, 1, en_US]
Figure 7-6
Detailed information on the clamp designations, for example 1A, is in the Hardware Manual and in the hard-
ware configuration.
In addition you can use the Current measuring points and Voltage measuring points window to add other
measuring points to the application.
218
Signal Flow Direction in the Fault Recorder
Route Measuring Points
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017