The logging of the respective status such as ensuing faults, test and diagnosis operation, and communication
capacity utilizations is done for all hardware-based configured communication interfaces. Up to 500 indica-
tions can be stored in the communication log. Logging occurs separately for each communication port of the
configured communication modules.
Reading from the PC with DIGSI 5
Use the project tree window to reach the communication logs of your SIPROTEC 5 device.
Online access → USB → Device → Test suite → Communication module
Then click J:Onboard Ethernet → Communication log.
The communication indications are displayed when you click the arrow under Time stamp.
The communication log is shown to you in the state last loaded from the device.
To update (synchronization with the device) click the button Update in the headline of the indication list.
[sccompuf-270213-01.tif, 1, en_US]
Figure 3-13
Reading on the Device through the On-Site Operation Panel
To reach the communication log from the main menu, use the navigation keys of the on-site operation
panel.
Main Menu → Test & Diagnosis → Indications → Communication log
You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
56
Reading the Communication Log with DIGSI 5
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017