Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Addr.
_:9721:103
_:9721:104
_:9721:114
_:9721:105
_:9721:106
_:9721:115
_:9721:107
_:9721:108
_:9721:116
_:9721:112
7.5.3.6

Information List

No.
Trigger f 1
_:9721:54
_:9721:52
_:9721:53
_:9721:301
7.5.4

Power Trigger

7.5.4.1

Overview of Functions

Power triggers start for the group triggers with exceeding or dropping below the set limiting values (level and
gradient trigger) in the fast-scan and slow-scan recorders. It is triggered on active power, reactive power,
apparent power, and power swing.
7.5.4.2

Structure of the Function

The Power trigger function is found in the 3-phase voltage/current function group, which is connected with
a 3-phase voltage and a 3-phase current measuring point.
The structure of the Power trigger function is shown in the following figure:
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Parameter
C
Trigger f 1:Min. trigger
active
Trigger f 1:Min. trigger
Trigger f 1:Min. trigger
hysteresis
Trigger f 1:dM/dt rise
active
Trigger f 1:dM/dt rise (/
Filter time)
Trigger f 1:dM/dt rise
hysteresis
Trigger f 1:dM/dt drop
active
Trigger f 1:dM/dt drop (/
Filter time)
Trigger f 1:dM/dt drop
hysteresis
Trigger f 1:Filter time
Information
Trigger f 1:Inactive
Trigger f 1:Behavior
Trigger f 1:Health
Trigger f 1:Trigger active
7.5 Trigger Functions 3-Phase
Setting Options
no
yes
25.000 Hz to 50.000 Hz
1.001 p.u. to 1.010 p.u.
no
yes
0.005 Hz to 60.000 Hz
0.990 p.u. to 0.999 p.u.
no
yes
0.005 Hz to 60.000 Hz
0.990 p.u. to 0.999 p.u.
2 cycles to 250 cycles
Data Class
(Type)
SPS
ENS
ENS
SPS
Fault Recorder
Default Setting
yes
49.600 Hz
1.002 p.u.
no
0.100 Hz
0.998 p.u.
no
0.100 Hz
0.998 p.u.
2 cycles
Type
O
O
O
O
335