Fault Recorder
7.5 Trigger Functions 3-Phase
Addr.
_:9691:112
Information List
7.5.1.10
No.
Trig. V fund 1
_:9571:54
_:9571:52
_:9571:53
_:9571:301
Trig. V RMS 1
_:9601:54
_:9601:52
_:9601:53
_:9601:301
Trigger V0 1
_:9631:54
_:9631:52
_:9631:53
_:9631:301
Trigger V1 1
_:9661:54
_:9661:52
_:9661:53
_:9661:301
Trigger V2 1
_:9691:54
_:9691:52
_:9691:53
_:9691:301
Current Trigger
7.5.2
7.5.2.1
Overview of Functions
Current triggers start with exceeding or dropping below the set limiting values (level and gradient trigger) in
the fast-scan and slow-scan recorders. It is triggered by fundamental values, RMS values, or on symmetrical
components.
7.5.2.2
Structure of the Function
The Current trigger function can be configured in the 3-phase voltage / current function group.. The struc-
ture of the function Current trigger is shown in the following figure:
312
Parameter
C
Trigger V2 1:Filter time
Information
Trig. V fund 1:Inactive
Trig. V fund 1:Behavior
Trig. V fund 1:Health
Trig. V fund 1:Trigger active
Trig. V RMS 1:Inactive
Trig. V RMS 1:Behavior
Trig. V RMS 1:Health
Trig. V RMS 1:Trigger active
Trigger V0 1:Inactive
Trigger V0 1:Behavior
Trigger V0 1:Health
Trigger V0 1:Trigger active
Trigger V1 1:Inactive
Trigger V1 1:Behavior
Trigger V1 1:Health
Trigger V1 1:Trigger active
Trigger V2 1:Inactive
Trigger V2 1:Behavior
Trigger V2 1:Health
Trigger V2 1:Trigger active
Setting Options
2 cycles to 250 cycles
Data Class
(Type)
SPS
ENS
ENS
SPS
SPS
ENS
ENS
SPS
SPS
ENS
ENS
SPS
SPS
ENS
ENS
SPS
SPS
ENS
ENS
SPS
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Default Setting
2 cycles
Type
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O