Fault Recorder
7.2 Function-Group Type Recorder
[sctrigra-280113-01.tif, 1, en_US]
Figure 7-20
7.2.4
Application and Setting Notes – General Settings
The following figure shows the memory splitting of the different recorders and the general settings of the FG
Recorder.
[sc_RecorderGeneral, 1, en_US]
Figure 7-21
Parameter: Scaling COMTRADE
Recommended setting value Scaling COMTRADE = Secondary values
With the Scaling COMTRADE parameter, you scale the fault-record data for the COMTRADE format. Possible
setting values are Primary values or Secondary values .
Memory Splitting
The maximum flash-memory capacity of the recorder is 15 GB.
Using the parameter Flash-memory size you can change the flash-memory capacity of each individual
recorder.
Several thousand recordings can be stored, depending on the flash-memory capacity.