Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

[dwmintri-140213-01.tif, 1, en_US]
Figure 7-41
a
Trigger rising edge
b
Trigger falling edge
c
End of the retrigger blocking time (Max. trigger)
d
End of the retrigger blocking time (Min. trigger)
e
End of the post-trigger time
f
End of the maximum record time
t
Time line
If the identical trigger reason (for example, Iph rms: C) occurs again during the retrigger blocking time, the
retrigger blocking time restarts. The fault record is not extended. A new recording is only possible once a
trigger occurs outside the expired retrigger blocking time (see the following figure).
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
A New Trigger Reason (Min. Trigger) Extends the Fault Record
Fault Recorder
7.2 Function-Group Type Recorder
259