Application And Setting Notes Trig V Fund (Fundamental Component) - Siemens SIPROTEC 5 Manual

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Mode
The trigger is switched on, off, or in test mode. In test mode, the fault records are marked with a test flag.
You can find more information on the mode in chapter
DIGSI 5
.
Measured Value
With the Measured value parameter, you define whether the function block analyzes the phase-to-phase
voltages V
, V
AB
BC
the function blocks V Fund. Trig and V RMS Trig.
NOTE
i
i
Take into account that the setting of the trigger in percent always related to the connection type phase-
to-phase.
Switching on Trigger Max./Trigger Min.
With the parameters Max. trigger active and Min. trigger active, you define whether the respec-
tive level trigger is active or inactive.
Trigger Max./Trigger Min.
With the parameters Max. trigger and Min. trigger, you define from which threshold value the acti-
vated level trigger starts a fault record.
Switch on dM/dt Rise - dM/dt Drop
With the parameters dM/dt rise active and dM/dt drop active, you define whether the respective
gradient trigger is active or inactive.
Filtering Time
With the Filter time parameter, you define the number of the periods with which the gradient is deter-
mined.
Gradient Trigger for Rising and Dropping Gradients of the Voltage
With the parameters dM/dt rise (/Filter time) and dM/dt drop (/Filter time), you define
from which threshold value within the set filtering time a fault record is started.
7.5.1.4

Application and Setting Notes Trig V Fund (Fundamental Component)

Parameter: Mode
Default setting (_:9571:1) Mode = off
With the Mode parameter, you activate the trigger for normal operation (On) or the test mode (Test).
Parameter Value
on
off
test
Parameter: Measured Value
Default setting (_:9571:9) Measured value = phase-to-phase
With the Measured value parameter, you define, independently of the connection type, whether to trigger
on phase-to-phase or phase-to-ground variables.
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
, and V
or the phase-to-ground voltages V
CA
Description
The function block Trig. V fund 1 is activated and the fundamental
component is monitored on the basis of the set trigger parameter.
The function block Trig. V fund 1 is deactivated.
The function block Trig. V fund 1 is activated for test purposes.
7.1.3 Step 2: Setting the Parameters and Routing in
, V
, and V
. This parameter can be adjusted in
A
B
C
Fault Recorder
7.5 Trigger Functions 3-Phase
299