Motor-side power components
10.1 Motor reactors
Danger to life due to electric shock in the event of missing touch protection
Death or serious injury can result when live parts are touched.
• For the motor reactors, use touch protection according to IPXXA or corresponding to the
Fire hazard due to overheating because of inadequate ventilation clearances
Inadequate ventilation clearances can cause overheating with a risk for personnel due to
smoke and fire. This can also result in increased failure rates and a shorter service life of
the components.
• Maintain the 100 mm clearances above and below the components.
Risk of burns due to high surface temperatures
The motor reactors can become very hot. You can get seriously burnt when touching the
surface.
• Mount the motor reactors so that contact is not possible. If this is not possible, attach
• To prevent adjacent components from suffering damage due to these high
Note
Maximum permissible output frequency
The maximum permissible output frequency when motor reactors are used is 120 Hz.
NOTICE
Damage caused by using incorrect motor reactors
When using motor reactors that have not been approved by Siemens for SINAMICS, the
motor reactors can be damaged.
• Only use motor reactors that SIEMENS has approved for operation with SINAMICS.
Note
Maximum cable length of the connection cables
The connection cables to the Motor Module must be kept as short as possible (max. 5 m).
590
DANGER
local installation regulations.
WARNING
CAUTION
clearly visible and understandable warning notices at hazardous positions.
temperatures, maintain a clearance of 100 mm on all sides of the motor reactors.
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6