Please note the following before mounting an Active Line Module with cold plate on a
customer-specific heat sink:
● Check the surface of the heat sink to ensure that it is not damaged.
● To improve heat transfer, a heat-conducting medium must be used. Special spherical-
Note
• Also replace the heat-conducting foil when replacing a component.
• Only use heat-conducting foil released or supplied by Siemens.
Table 4- 32
Heat-conducting foil, 50 mm
Heat-conducting foil, 100 mm
Heat-conducting foil, 150 mm
Heat-conducting foil, 200 mm
Heat-conducting foil, 300 mm
Note
M6 studs and hexagon nuts or grub screws (ISO 7436-M6x40-14 H, property class 8.8) are
recommended for mounting the components.
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
indented heat-conducting foil must be used for this purpose. Every component with cold
plate is supplied with heat-conducting foil cut to the right size. Note the mounting position
of the heat-conducting foil (see diagram below).
Overview of heat-conducting foils
4.4 Active Line Modules with cold plate
Order number
6SL3162-6FB00-0AA0
6SL3162-6FD00-0AA0
6SL3162-6FF00-0AA0
6SL3162-6FH00-0AA0
6SL3162-6FM00-0AA0