Line Modules Booksize
4.4 Active Line Modules with cold plate
4.4.2.3

X21 EP terminals

Table 4- 26
X21 EP terminal / temperature sensor
Terminal
1
2
3
4
Type: Screw terminal 1 (Page 755)
Max. cross-section that can be connected: 1.5 mm
The temperature sensor type and the temperature output can be selected by parameter (see the SINAMICS S120/S150
1)
List Manual).
Temperatures are detected but not evaluated in the Active Line Module.
2)
Terminals X21.1 and X21.2
When using an Active Interface Module, the temperature output of the Active Interface
Module must be connected at terminals X21.1 and X21.2.
Terminals X21.3 and X21.4
Danger to life when live parts are touched when terminals X21.3 and X21.4 are connected
For operation, the 24 V DC voltage must be connected to terminal X21.3 and ground to
terminal X21.4.
Pulse cancellation is activated if the power supply is disconnected. Regenerative feedback
is deactivated and the bypass relay drops out. If the Line Module is not disconnected from
the line supply when the EP terminal is de-energized, for example, because a line contactor
is not installed, then the DC link remains charged.
Death or serious injury can result when live parts are touched.
• Neutralize the voltage in the DC link.
202
Designation
+ Temp
- Temp
EP +24 V (pulse enable)
EP M (Enable Pulses)
WARNING
Technical data
Temperature sensors
1C130
/PTC
2)
If an Active Interface Module is used, the temperature
input must be connected to the Active Interface Module
sensor (bimetallic switch with NC contact).
Voltage: 24 V DC
Current consumption: 10 mA
Isolated input
Signal propagation times:
L → H: 100 μs
H → L: 1000 μs
2
: KTY 84–
1)
/bimetallic switch with NC contact
2)
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6