Maximum cable lengths

The table below provides an overview of the maximum permissible cable lengths for signal
and supply cables, power cables, and DC link cables.
Table 12- 21 Maximum cable lengths
Type
24 V DC supply cables
1)
24 V signal cables
1)
DRIVE-CLiQ signal cables MC500 (RJ45)
DRIVE-CLiQ signal cables MC500 (M12)
DRIVE-CLiQ signal cables MC800PLUS (RJ45)
DRIVE-CLiQ signal cables MC800PLUS (M12)
DC link, including extensions
Total cable length for Active Line Modules 16 ... 36 kW with
Active Interface Module
4)
Total cable length for Active Line Modules 55 ... 120 kW with
Active Interface Module
4)
Total cable length for Active Line Modules with line reactor
Total cable length for Basic Line Modules
Total cable length for Smart Line Modules
Power cable between line filter and line reactor
Power cable between line reactor and Line Module
Power cable between
motor and Motor Module up to I
Power cable between
motor and Motor Module I
Power cable between
motor and Motor Module I
Cable between the Braking Module and braking resistor
For longer lengths, the user must connect a suitable protective circuit in order to provide overvoltage protection (refer to
1)
the chapter "Overvoltage protection" under "24 V DC supply")
To comply with EMC limit values, shielded cables (preferably MOTION CONNECT cables) must be used.
2)
Restrictions regarding the total cable length and the secondary conditions required to comply with the corresponding
3)
radio interference suppression category are listed in Chapter "Possible line reactor and line filter combinations".
The total lengths specified for power cables in the drive line-up include motor cables, DC link cables, and the line feeder
4)
cable, line filter to the Line Module.
Note
Total cable lengths
also referred to Basic Line filter for Active Line Modules (Page 62) as well as Possible line
reactor and line filter combinations (Page 136).
742
4)
4)
= 9 A
n
= 18 A
n
≥ 30 A
n
4)
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
Maximum length [m]
10
30
100
30
75
30
10
630 (shielded)
3)
1000 (shielded)
3)
350 (shielded)
3)
630 (shielded)
3)
350 (shielded)
3)
10 (shielded/unshielded)
2)
10 (shielded/unshielded)
2)
50 (shielded)
75 (unshielded)
70 (shielded)
100 (unshielded)
100 (shielded)
150 (unshielded)
10
Booksize Power Units