Technical Data - Siemens Sinamics S120 Manual

Booksize power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

4.7.8

Technical data

Table 4- 62
Technical data for Basic Line Modules with cold plate cooling
Rated power
Infeed
Rated power (S1)
1)
Infeed power (S6 - 40 %)
Peak infeed power
1)
Braking power
Continuous power
Peak power
Supply voltages
Line voltage
Line frequency
Electronics power supply
DC link voltage
Overvoltage trip
Undervoltage trip
2)
Rated input currents
at AC 380 V
at AC 480 V / AC 528 V
at 480 V; S6 - 40 %
Peak current
at AC 400 V / AC 480 V)
DC link currents
Rated DC link current:
for 600 V
DC link current:
for 540 V
for DC 600 V; S6 - 40 %
for DC 600 V; peak current
Current carrying capacity
DC link busbars
Reinforced DC link busbars
24 V DC busbars
Electronics current drawn
at 24 V DC
Total power loss
(including electronics losses, see Power
loss tables (Page 781))
DC link capacitance
Basic Line Module
Drive line-up, max.
Power factor
3)
Circuit breaker
(IEC 60947 and UL)
Rated short-circuit current
SCCR
4)
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
6SL3136-
kW
kW (P
kW (P
1)
kW (P
kW (P
kW (P
V
ACrms
Hz
V
DC
V
DC
V
DC
V
DC
A
AC
A
AC
A
AC
A
AC
A
DC
A
DC
A
DC
A
DC
A
ACrms
A
ACrms
A
ACrms
A
DC
W
μF
μF
cosϕ
kA
1TE22-0AA0
20
)
20
n
)
26
S6
)
60
max
)
5
n
)
40
max
3 AC 380 ... 480 ± 10 % (-15 % < 1 min)
47 ... 63
24 (20.4 ... 28.8)
510 ... 720
820 ± 2 %
360 ± 2 %
34,5
31 / 29
38
113 / 91
33,5
37
43
100
100
150
20
0,9
141,6
940
20000
Approx. 0.98
See Section Overcurrent protection using line fuses and
circuit breakers (Page 51)
65
Line Modules Booksize
4.7 Basic Line Modules with cold plate
1TE24-0AA0
1TE31-0AA0
40
100
40
100
52
130
120
175
10
-
80
-
69
172
62 / 58
154 / 145
78
193
208 / 172
265 / 252
67
167
48
185
87
217
200
292
200
200
--
--
20
20
1,1
1,6
276,4
618,4
1880
4100
20000
20000
65
65
269