Siemens Sinamics S120 Manual page 87

Booksize power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

NOTICE
Damage to the system caused by line reactors that are not permissible
Line reactors that are not permissible can damage the Line Modules.
Line harmonics that damage/disturb other loads connected to the same line supply can also
occur.
• Only use line reactors or Active Interface Modules described in this manual.
Note
Malfunctions through magnetic fields
Reactors produce magnetic fields that can disturb or damage components and cables.
• Arrange the components and cables at a suitable distance (at least 200 mm) or shield the
Note
Length of connecting cables
The connection cables between line reactor and Line Module, as well as between line
reactor and line filter, must be kept as short as possible (max. 10 m).
You must use shielded connection cables, whose cable shields are attached at both ends.
Shielding can only be omitted if the following conditions are met:
• The cables do not exceed 1 m in length.
• The cables are laid flush with the rear metal wall of the control cabinet.
• The cables are laid in a way that keeps them physically separate from signal cables.
Do not route any cables near the line reactor. If this cannot be avoided, observe a minimum
distance of 200 mm.
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
magnetic fields appropriately.
Line connection and line-side power components
3.8 Line reactors
87

Advertisement

Table of Contents
loading

Table of Contents